porte sectionnelle pare flamme et coupe-feu EI 60/EI 90
Sectional fireproof and fire-resistant door EI 60/EI 90
Features
Reference
PRT-05-06
Durée de résistance au feu
EI 30/60 min - EW 90 min 1
Hauteur maxi
5000 mm 1
Moteur
gravitaire 220 ou 400 volts 1
Couleur
RAL au choix
Epaisseur
40 mm 1
Largeur maxi
4500 mm 1

Fire-resistant sectional door with fire and flame retardant EI 60/EI 90. CE marking EN-13241/EN-16034

Technical description

The EI 60/EI 90 fire-resistant and fire-rated sectional door is a reliable and effective solution for ensuring fire safety in various environments.

  • Certification: tested in accordance with standard: EN 1634-1
  • Classified according to standard: EN 13501-2
  • Fire class: B-s1, d0 according to standard EN 13501-1
  • Cycle test: Validated according to standard C3 (> 50,000 cycles)
  • CE marking: Compliant with standards EN 13241 and EN 16034.

The EI 60/EI 90 fire-resistant and fire-rated sectional door is designed for indoor and outdoor use. It is ideal for protected evacuation routes, although not intended for use as a main evacuation route.
Suitable for frequent use and can be mounted on the wall or opening.

Approved mounting surfaces include aerated concrete, silico-calcareous brick, concrete, masonry, and fire-resistant steel constructions.

2 types of motorization:

  • Standard motor: 400 V fail-safe gravity chain motor with control unit and integrated battery.
  • External tubular motor 230 V with gravity descent and control unit (up to ± 11 m²)

Safety device: Optical and acoustic signaling

Door curtain: Made of fire-resistant composite panels, 80 mm thick, with a white mixed structure

Anti-burglary version: Exterior to interior according to RC 2 or RC 3

Sound insulation: 29 dB value

Rail systems:

  • Extra low for installation height of 500 mm to 780 mm
  • Low for installation height of 780 mm to 1,100 mm
  • Vertical or high for installation from 1,600 mm

Options:

  • Panels: Available in your choice of RAL color, applied by wet painting
  • Barrier and hardware set
  • Smoke detector: with standalone system
  • Various switches
  • Explosion-proof components and marking (ATEX)

Contact us for more information or for a custom configuration tailored to your specific needs.

Sectional fireproof and fire-resistant door EI 60/EI 90

Features
Reference
PRT-05-06
Durée de résistance au feu
EI 30/60 min - EW 90 min 1
Hauteur maxi
5000 mm 1
Moteur
gravitaire 220 ou 400 volts 1
Couleur
RAL au choix
Epaisseur
40 mm 1
Largeur maxi
4500 mm 1

Questions & Answers

Why opt for a sectional door rather than a curtain?

A sectional door is more insulating than a metal curtain

How long does a sectional door or curtain last?

A sectional door can do 20 cycles per day with a limit of 25,000 cycles, a metal curtain can do 10 cycles per day with 10,000 cycles.

What is the AEV classification?

The AEV class is the European standard for air, water and wind tightness. Each door must have its classification notified on a label affixed to the product.

What is the purpose of a fire-resistant sectional door?

A fire-resistant sectional door isolates one compartment from another, preventing the spread of flames, smoke and heat.

What is CE marking?

CE marking guarantees the user or customer that the product complies with safety and quality standards. Marking is compulsory before a product can be placed on the market.

What are the abbreviations E, EW and EI?

Products bearing the EEW and EI labels in accordance with European standards are valid. E (tightness) EW (flame-tightness) and EI (heat-tightness /below 140°)

What dimensions are authorised?

The maximum authorised dimensions are notified in the PVs approved by the test laboratories.